Description
Outdoor remote metering enclosure with galvanized steel enclosure, designed in accordance with SEC Specification 42-SDMS-01A Rev. 2.3.
Technical Specifications
| Parameter | 200/250A CT Meter box | 300/400A CT Meter box | 500/600A CT Meter box |
| SEC Item | 908421036 | 908421033 | 908421034 |
| Overall Dimensions (W × H × D), mm | 592 x 1053 x 254 | 692 x 1053 x 254 | 692 x 1053 x 254 |
| Net Weight, kg | 60 | 70 | 70 |
| Enclosure Material | Galvanized Steel, G90 coating | Galvanized Steel, G90 coating | Galvanized Steel, G90 coating |
| Rated Operational Voltage (Ue), V AC | 400V | 400V | 400V |
| Rated Frequency, Hz | 60 Hz | 60 Hz | 60 Hz |
| Rated Insulation Voltage of internal wiring/terminals, V | 1000 V | 1000 V | 1000 V |
| Ingress Protection Rating | IP54 | IP54 | IP54 |
| No.Type of Meter | 1 x CT Meter | 1 x CT Meter | 1 x CT Meter |
| Meter Circuit-Breaker Rating | Rated up to 250 A | Rated up to 400 A | Rated up to 600 A |
| Meter box Continues Current Rating | 200 A | 400 A | 600 A |
STANDARDS & COMPLIANCE
- IEC 61439-5 — Low-voltage switchgear and control gear assemblies, Part 5: Assemblies for public electricity network distribution (PENDA).
- SEC Specification 42-SDMS-01, Rev. 2.3 — Saudi Electricity Company particular specification for LV meter box construction.
- SEC Specification 01-SDMS-01 — SEC outdoor-installation / environmental requirement referenced for the enclosure’s IP54 rating.
- ISO 12944 — Corrosion protection of steel structures by protective paint systems (corrosivity category C5).
STANDARDS & COMPLIANCE
| Parameter / Item | Specification / Details |
| Standard | SEC Specification 42-SDMS-01A Rev. 2.3 — Meterbox with Steel Enclosures. |
| Standard | IEC 61439-5 — reference standard stated in the SEC technical data schedule. |
| Standard | IEC 60947-7-1 — applicable type-test standard for terminal blocks. |
| Standard | IEC 60228 and related standards — applicable to the specified internal/fire-resistant wiring. |
| Standard | ISO 12944-6 — laboratory performance testing of the corrosion-protection paint system. |
OPERATING CONDITIONS
| Parameter / Item | Specification / Details |
| Installation | Outdoor operation |
| Solar Exposure | Suitable for direct solar radiation; exposed surface temperature is regarded as 75°C plus internal heating effects. |
| Ingress Protection | IP54 |
| Mounting | Semi-flush and direct wall-mounting |
| Ventilation | Natural air circulation through side/removable-bottom louvers with stainless-steel screening. |
INSTALLATION & MAINTENANCE
| Parameter / Item | Specification / Details |
| Requirement | Provide the specified stainless-steel wall-mounting brackets and fasteners. |
| Requirement | The remote meterbox has three M8 threaded blind nodes for mounting-bracket fixation. |
| Requirement | Main current-carrying conductors are not part of the remote meterbox; they are located in the Service Cabinet. |
| Requirement | Internal wiring shall be organized and supported; conductor color coding follows the SEC schedule. |